Offices & administrative buildings

Office buildings with server rooms, archives and basement parking.

What we install & maintain

The systems for this type of space

An office building is full of people during working hours and empty at night — and has a server room that cannot take water. We handle fire detection, hydrant systems, suppression for equipment rooms, extinguishers and security systems, from design to maintenance.

Regulatory framework

What governs this type of space

Occupancy categoryOffices (P.D. 41/2018, Ch. B, art. 8).
Fire extinguishersOne per 150 m² gross area (8.4.1).
Manual fire alarmWith a design occupancy over 100 people (8.4.2).
Automatic fire detectionOver 200 occupants, or with three or more floors of main use (8.4.3).
Fire hydrant systemPermanent hydrant system with four or more floors and at least 3,000 m²; from 5,000 m²; over 20 m high. Otherwise a hose cabinet (8.4.4).
SprinklersIn office buildings over 23 m high (8.4.5).
Server roomPortable CO₂ near electrical equipment and computers (Fire Service Ordinance 15/2014, 4.1.1.2); where sprinklers are required and water is unsuitable, another agent is allowed (P.D. 41/2018, Ch. A, 7.2.3).
Existing officesPermit applied for before 17-2-1989: Fire Service Ordinance 17/2016. On a total change of use, or an extension over 50% of the main-use area and over 300 m², P.D. 41/2018 applies (Ch. A, 2.1 d-e). Monuments, listed and traditional buildings: always the Fire Service Ordinance (Ch. A, 2.3).

Which framework binds a given building depends on the date the building permit was applied for and on its occupancy classification. The binding requirement comes from the approved fire-safety study.

From our projects

Where we have done this

Hellenic State

Ministry of Maritime Affairs and Insular Policy

Supply of firefighting equipment

Supply of firefighting equipment for the Ministry's central facilities.

Hellenic State

Ministry of Education, Religious Affairs and Sports

Fire extinguisher maintenance at the Ministry's buildings

Certified inspection, maintenance and refilling of fire extinguishers at the Ministry's buildings in Attica.

ELEMKA S.A.

AADE headquarters (former Athens Heart)

Supply of firefighting equipment

Supply of fire extinguishers, fire hose cabinets, firefighting equipment stations and fire suppression systems.

Frequently asked questions

Offices & administrative buildings — what clients ask us

When do offices need fire detection?

In a new building, when the design occupancy exceeds 200 people or the offices spread over three or more floors. A manual fire alarm is already required when the design occupancy exceeds 100 people.

How is the server room protected?

With detection and, where needed, a fixed gaseous or aerosol suppression system that extinguishes without harming the equipment. Nearby, portable CO₂ extinguishers.

Do you also maintain the extinguishers?

Yes — annual maintenance, refilling and logbook updates, within Attica.