Application

Hotels & tourist accommodation

Sleeping occupants, many compartments and kitchens — every system working together.

What we install & maintain

The systems for this type of space

A hotel is full of people asleep in a building they do not know. That is why the code requires early warning, clear escape routes and fire-fighting means on every floor. We take on the whole package — design, supply, installation and maintenance of fire detection, hydrant and sprinkler systems, kitchen suppression and extinguishers — with specialised crews and a single point of responsibility.

Regulatory framework

What governs this type of space

Occupancy categoryTemporary accommodation — from 20 beds (P.D. 41/2018, Ch. B, art. 2). Smaller premises are treated as residential.
Fire extinguishersOne portable dry powder or water-based extinguisher per 100 m² gross area (2.5.1).
Manual fire alarmIn all hotels (2.5.2).
Automatic fire detectionFrom 50 beds, or with two or more floors of main use (2.5.3).
Fire hydrant systemPermanent hydrant system with three or more floors of main use and at least 100 beds, and in campsites located within, or less than 300 m from, a forest or forest land; otherwise a simple system with a fire hose cabinet (2.5.4).
SprinklersIn buildings over 23 m high, or with three or more floors of main use and at least 300 beds (2.5.5).
Lighting & signageEmergency lighting of escape routes and exits, safety signs, and an escape plan in every room (2.4).
Existing hotelsPermit applied for between 17-3-1988 and 7-8-2018: P.D. 71/1988 art. 6 (for buildings hosting fewer than 20 persons, requirements are set case by case by the competent authority — art. 6 §1). Before 17-3-1988: Ch. B of P.D. 71/1988 (arts 16-22).

Which framework binds a given building depends on the date the building permit was applied for and on its occupancy classification. The binding requirement comes from the approved fire-safety study.

From our projects

Where we have done this

TEMES · Ionian Hotel Enterprises

Conrad Athens — The Ilisian

Fire extinguishers, certified fire hose cabinets & equipment stations

Supply of portable fire extinguishers, certified fire hose cabinets and firefighting equipment stations.

Xenodocheio Milos

Xenodocheio Milos, Athens

Supply of all fire-protection equipment

Supply of all fire-protection equipment for the hotel and the restaurant: fire detection, voice alarm (PAVA), gas detection, fixed fire suppression systems, kitchen fire suppression and fire pump set.

Xenodocheio Milos · AKTOR FM

Xenodocheio Milos, Athens

Annual maintenance of all systems

Annual maintenance of fire detection, voice alarm (PAVA), gas detection, fixed fire suppression systems, kitchen fire suppression and the fire pump set — hotel and restaurant in the same building.

Frequently asked questions

Hotels & tourist accommodation — what clients ask us

Which code applies to my hotel?

It depends on the date the building permit was applied for. After 7-8-2018, P.D. 41/2018 applies; from 17-3-1988 until then, P.D. 71/1988; older hotels fall under Chapter B of P.D. 71/1988. If works are carried out in an existing hotel under a building permit applied for after 7-8-2018, P.D. 41/2018 applies: to a functionally independent extension (the extension only); in a hotel designed to art. 6 of P.D. 71/1988, to a change of use or a functionally dependent extension; in a hotel whose permit predates 17-3-1988, only to a change of use of the whole building or a dependent extension exceeding both 50% of the existing building's main-use area and 300 m². Renewing the fire certificate without new works does not require a new study under P.D. 41/2018. There is no longer a separate Fire Service Ordinance for hotels.

From how many beds is automatic fire detection required?

In a new hotel (P.D. 41/2018), from 50 beds — or sooner, if the building has two or more floors of main use. A manual alarm system is required in every hotel.

Does the kitchen need a fire suppression system?

Local suppression for commercial kitchens and its specification are set by Fire Service Ordinance 15/2014 and the fire study. We design, install and maintain the complete system — not just the cylinder.

Can you take on all of the hotel's fire protection?

Yes. Systems anywhere in Greece, with one point of responsibility from design to maintenance. Extinguisher maintenance and refilling is carried out within Attica.

Need a quote for your space?