Non-ambulatory patients, medical gases and horizontal evacuation between compartments.

What we install & maintain

The systems for this type of space

In hospitals and clinics many patients cannot leave on their own. That is why the code requires detection throughout the building, a fire control point staffed around the clock and higher emergency-lighting requirements in operating theatres and ICUs. We design, supply, install and maintain fire detection, hydrant and sprinkler systems, gas detection and passive fire protection.

Regulatory framework

What governs this type of space

Occupancy categoryHealthcare and social welfare (P.D. 41/2018, Ch. B, art. 5): E1 welfare · E2 no in-patient beds or theatres · E3 hospitals, clinics, health centres.
Fire extinguishersOne per 100 m² gross area (5.5.1).
Automatic fire detectionIn all E1 and E3 buildings; in E2 with three or more floors or over 200 occupants. Standby battery for at least 30 hours of operation (5.5.3).
Manual fire alarmIn all E1 and E3 buildings; in E2 with over 100 occupants (5.5.2).
Fire control pointIn E3 buildings, in a room staffed around the clock (5.5.5).
Fire hydrant systemPermanent hydrant system in buildings over 20 m high; in E1/E2 with four or more floors and at least 3,000 m², or over 5,000 m²; in E3 with over 100 beds and the top floor more than 12 m up. Otherwise a simple system with a hose cabinet (5.5.4).
SprinklersIn E3 basements with over 150 occupants (including their unprotected escape routes), in E1 over 500 m² and in E1/E2 over 23 m high (5.5.6).
Emergency lightingIn all categories; ICUs, neonatal units, operating and delivery suites are treated as high-risk task areas under EN 1838 (5.4.2).
Existing buildingsPermit applied for before 17-2-1989: Fire Service Ordinance 18/2019 — e.g. one extinguisher per 100 m² in E1/E2 and per 150 m² in E3.

Which framework binds a given building depends on the date the building permit was applied for and on its occupancy classification. The binding requirement comes from the approved fire-safety study.

Frequently asked questions

Hospitals & clinics — what clients ask us

Which category does my facility fall into?

E3 if it has in-patient beds, operating theatres or recovery areas (hospitals, clinics, dialysis units). E2 if it only provides prevention, diagnosis or day treatment without overnight stay (diagnostic centres, polyclinics). Exception: simple doctors' surgeries, regional surgeries and dental practices with no in-patient bed, isotope unit, radiology lab or physiotherapy facilities are assessed as Offices (P.D. 41/2018, 5.1). E1 covers welfare buildings (care homes, nurseries). In case of doubt, the competent Directorate of the Ministry of Environment and Energy decides.

Why does fire detection need a 30-hour battery?

The code (P.D. 41/2018, 5.5.3) requires a standby source that keeps the system running for at least 30 hours, so protection continues during a power cut. Battery sizing is part of the system design.

What applies to an older clinic building?

If the permit was applied for before 17-2-1989, Fire Service Ordinance 18/2019 applies. In such a building, P.D. 41/2018 applies only in three cases: a functionally independent extension, a change of use of the whole building, or a dependent main-use extension that exceeds 50% of the existing main-use area and is also over 300 m². Smaller dependent extensions, partial changes of use and renovations stay under Fire Service Ordinance 18/2019.

Do you also handle gas detection?

Yes — detectors for boiler rooms, kitchens and areas with oxygen or inert gases, together with periodic calibration and its certificate.