ON LINE SUPPORT Ελληνικά English
Products
Subscribe »
User name
Password
Forgot password? »
 
SERVICES
FIREFIGHTING - EXTINGUISHING
Fire Extinguishers
Fire Cabinets, Stations & Equipment
Fire Suppression Systems
DSPA Aerosol Generators
Cooks Fire Suppression Local Application Systems
Wet Chemical Fire Suppression System "ZEUS"
Wet Chemical Fire Suppression System "ACHILLES"
Wet Chemical Fire Suppression System "PROMETHEUS"
CO2 Fire Suppression Systems
IG541 Fire Suppression Systems
SIEX Permanent HFC227EA Systems
KIDDE Permanent FM200 Systems
KIDDE Permanent NOVEC 1230 Systems
INERGEN TYCO MARINE Permanent Systems
Fire Suppression Systems Components
Fire Safety Doors
Fireman Equipment - Safety - First Aid Equipment
Extinguishing Agents & Fire Retardant Liquids
FIRE DETECTION
GAS DETECTION
SPRINKLERS - FIREFIGHTING NETWORK ACCESSORIES
ACCESS CONTROL - SECURITY CAMERAS
EMERGENCY LIGHTING
 
Trade marks
» Kentec Electronics
» KIDDE
» Mobiak
» Olympia Electronics
» Sensitron
» SIEX
» Teletek Electronics
» Tyco Fire & Building Products
» Unimarsafe

Wet Chemical Fire Suppression System "ACHILLES"


In this type of System, in automatic operation, thermal sensitive fusible detectors in row are used for detecting fire . The Suppression Agent is been distributed over the protected areasappliances and inside the exhaust funnel through an ISO Copper Piping and Special Type Discharge Nozzles.

In case the system consists of more than one Local Application Fire Extinguishers, the operation of each extinguisher is been achieved using a fuse-detonator. In both automatic and manual activation, the system can be programmed to shut off the electrical power and the gas-propane supply in all or in selected devices for maximum protection against re-ignition.

Automatic Operation

In case of fire, the breaking-melting of any thermal sensitive fusible detector (138°C or 182°C or 260°C), activates the system by electro-mechanical means. The fusible detectors are connected in a row-form through a stainless steel metal wire. The first end of the metal wire is fixed to the exhaust hood while the other end is connected to an electromechanical position switch. In normal condition, the metal wire is stretched and it pulls the contact of the position switch. In case of fire, the fusible of a detector breaks-melts and the metal wire that connects the detectors with the position switch gets loosen. The position switch gets activated and it activates through the Fire Detection Panel of the System the Fire Extinguisher Valve (through the fusedetonator) and then the Suppression Agent is been distributed through the Copper Pipping and the Special Type Discharge Nozzles over the Protected Areas.

Manual Operation

Incase of fire, the manual activation of the system can be done in three (3) different ways (1) Pressing of special manual system activation button that is built-in into the fire detection panel, (2) Pulling of remote control mechanical metal wire handle and (3) Pulling of the fire extinguisher valve rod towards the ground-floor.

The system includes

  • Fire Extinguishers with Internal Plastic Layer of 6 and 9ltr capacity
  • Fire Extinguishers made of Stainless Steel of 10ltr (12kgr vessel) capacity.
  • Fire Extinguishers with Anticorrosive Internal Paint of 20ltr (25kgr vessel) and 35ltr (50kgr vessel) capacity.
  • Heavy duty support base/bracket for mounting the Fire Extinguisher.
  • Fire extinguisher certified valve of manual or automatic activation with safety relief valve, certified according CE-TUV.
  • Flexible stainless steel hose (21,7mm x 1/2”) for connecting the fire extinguisher valve with the pipe network.
  • Thermal-sensitive fusible detectors (138°C or 182°C or 260°C).
  • Detector bases.
  • Stainless Steel metal wire and clutches.
  • Remote control mechanical handle.
  • 90ο metal wire guide roller.
  • One Zone Fire detection panel with built-in Siren, Battery and Manual System Activation Button.
  • Electro-mechanical position switch.
  • Extinguish cancel button.
  • Gas/Propane Electro-mechanical switching valve.
  • Special discharge nozzles.
  • Male couplings (1/2”x 3/8”) for connecting the nozzles with the pipe network.